Mô đun 1756-OB32
Thông số kỹ thuật allen bradley 1756-OB32
Attribute | 1756-OB32 |
Outputs | 32 (16 points/group) |
Voltage category | 12/24V DC source |
Operating voltage range | 10..,31.2V DC |
Output delay time Off to On | 60 ps nom/1 ms max |
On to Off | 200 ps nom/1 ms max |
Current draw @ 5.1V | 300 mA |
Current draw @ 24V | 2 mA |
Total backplane power | 1.58 W |
Power dissipation, max | 4.8 W @ 60 °C (140 °F) |
Thermal dissipation | 16.37 BTU/hr |
Off-state leakage current per point, max | 0.5 mA per point |
On-state voltage drop, max | 200 mV DC @ 0.5 A |
đại lý 1756-OB32 | nhà phân phối 1756-OB32 | module 1756-OB32
Technical Specifications – 1756-OB32 (continued)
Attribute | 1756-OB32 |
Current per point, max | 0.5 A @ 50 °C (122 °F) linear derating
0.35 A@ 60 °C (140 °F) |
Current per module, max | 16 A @ 50 °C (122 °F) linear derating
10 A @ 60 °C (140 °f) |
Surge current per point, max | 1 A for 10 ms per point, repeatable every 2 s @ 60 °C (140 °F) |
Load current, min | 3 mA per point |
Scheduled outputs | Synchronization within 16.7 s max, reference to the Coordinated System Time |
States in Fault mode per point | Hold last state, On or Off (Off is default) |
States in Program mode per point | Hold last state, On or Off (Off is default) |
Isolation voltage | 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs
Routine tested @ 1350V AC for 2 s |
Module keying | Electronic, software configurable |
Fusing | Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system that uses other wiring termination methods can require application-specific approval by the certifying agency. |
Removable terminal block | 1756-TBCH
1756-TBS6H |
RTB keying | User-defined mechanical |
Slot width | 1 |
Wire category | 1(1) |
North American temperature code | T3C |
IEC temperature code | T3 |
Enclosure type | None (open-style) |
(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications – 1756-OB32
Attribute | 1756-OB32 |
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) |
0.60 °C (32.140 °F) |
Temperature, surrounding air, max | 60 °C (140 °F) |
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) |
-40.+85 °C (-40.+185 °F) |
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) |
5.95% noncondensing |
Vibration
IEC 60068-2-6 (Test Fc, Operating) |
2 g @ 10.500 Hz |
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock) |
30 g |
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock) |
50 g |
Emissions | CISPR 11, Class A |
Đánh giá
Chưa có đánh giá nào.